ASCE 7-22 · DESIGN METHODS
C&C vs MWFRS — two checks, one building
The structural frame carries the whole building's wind. The cladding fights it panel by panel. ASCE 7 makes you check both.
THE DISTINCTION
One system carries the whole load. One element takes the local hit.
MWFRS averages wind across large surfaces. C&C concentrates it on a single window, panel, or fastener.
SIDE BY SIDE
Same wind, two procedures
Both start from the same velocity pressure, then diverge on coefficients, areas, and where pressures peak.
| Characteristic | MWFRS | C&C |
|---|---|---|
| What it covers | Frames, shear walls, diaphragms, foundations — the whole system carrying overall wind | Windows, doors, roof panels, fasteners, cladding — elements receiving wind directly |
| Coefficient | Cp (directional) or GCpf (envelope) | GCp |
| Effective wind area | Large — averaged over whole faces | Small — per component, by zone |
| Where pressures peak | Lower, averaged across the surface | Highest at corners & edges (Zone 3 roof, Zone 5 wall) |
| ASCE 7-22 chapter | Ch 27 Fig 27.3-1 (directional) · Ch 28 Fig 28.3-1 (envelope) | Ch 30 |
WHY C&C RUNS HIGHER LOCALLY
Small area + corner zones = peak pressure
Both methods use the same velocity pressure. C&C diverges because tiny areas at separation corners see concentrated gusts.
Smaller effective area
A single panel can't average gusts the way a whole face does, so its GCp climbs as area shrinks.
GCp ↑ AS AREA ↓Corner & edge zones
Flow separation and vortices spike suction at roof Zone 3 and wall Zone 5 — the highest local coefficients.
ZONE 3 / ZONE 5Peak suction values
Verified GCp peaks: roof Zone 3 −3.2 and wall Zone 5 −1.4, both at a 10 sq ft effective wind area.
−3.2 ROOF · −1.4 WALLShared basis. Both procedures use the same velocity pressure qh = 0.00256 · Kz · Kzt · Kd · Ke · V², with Kd = 0.85 and gust factor G = 0.85 for rigid buildings. Only the coefficient and effective area change.
NON-NEGOTIABLE
You check the same building twice
MWFRS pressures are lower and averaged — never use them to size cladding. C&C pressures are local and never represent the whole-building load path. A complete design runs both: MWFRS for the structure, C&C for every envelope element.
NEXT STEPS
Run both checks the right way
Pin down your method, then size the structure and the envelope.