ASCE 7-16 & ASCE 7-22 Chapter 29

Solar Panel Wind Load Calculations

Complete guide to designing rooftop and ground-mounted PV systems for wind loads per ASCE 7-16 and ASCE 7-22, including GCrn coefficients, roof zones, and the new Section 29.4.5 provisions.

Get Solar Panel Calculator

Introduction to Solar Panel Wind Loads

Solar photovoltaic (PV) systems must be designed to resist wind loads per ASCE 7 (Minimum Design Loads and Associated Criteria for Buildings and Other Structures). With the rapid growth of solar installations, ASCE 7-16 introduced dedicated provisions for solar panels, and ASCE 7-22 expanded these requirements further.

This guide covers wind load calculations for both rooftop-mounted PV systems and ground-mounted solar arrays, explaining the differences between ASCE 7-16 and ASCE 7-22, the applicable sections, and step-by-step calculation procedures.

ⓘ Why Solar Panel Wind Loads Matter

Solar panels create unique aerodynamic conditions on rooftops. They can experience significant uplift forces, and their mounting systems must resist both uplift and sliding. Improper design can lead to panel damage, roof damage, or even panels becoming windborne debris during high-wind events.

📖 ASCE 7 Sections for Solar Panels

Both ASCE 7-16 and ASCE 7-22 address solar panel wind loads in Chapter 29 (Wind Loads on Building Appurtenances and Other Structures). The key sections are:

Section Application ASCE 7-16 ASCE 7-22
29.4.3 Rooftop panels on flat or low-slope roofs (< 7°)
29.4.4 Rooftop panels on steeper roofs (≥ 7°)
29.4.5 Ground-mounted solar arrays (fixed-tilt) ✔ (NEW)

✔ ASCE 7-22 Adoption Status

ASCE 7-22 is referenced in the 2024 International Building Code (IBC) and International Residential Code (IRC). Florida has already adopted ASCE 7-22, and other states are expected to follow as they adopt the 2024 codes.

🔢 Design Wind Pressure Formula

The design wind pressure for rooftop solar panels per ASCE 7 is calculated using:

p = qh × GCrn
p = design wind pressure (psf)
qh = velocity pressure at mean roof height (psf)
GCrn = net pressure coefficient for solar panels

The net pressure coefficient GCrn is the product of several gamma (γ) factors:

GCrn = γp × γc × γE × GCrn,nom
γp = parapet factor
γc = chord length (configuration) factor
γE = edge/exposure factor
GCrn,nom = nominal net pressure coefficient from Figure 29.4-7

Gamma Factor Details

γp

Parapet Factor

γp = min(1.2, 0.9 + hpt/h)

Where hpt is parapet height and h is building height. For buildings without parapets, γp = 0.9

γc

Chord Length Factor

γc = max(0.6 + 0.06×Lp, 0.8)

Where Lp is the panel chord length (ft). Accounts for panel size effects.

γE

Edge Factor

γE = 1.5 for exposed panels within 1.5×Lp from array edge (uplift only)

γE = 1.0 elsewhere and for all downward loads

GCrn,nom

Nominal Coefficient

From Figure 29.4-7 based on:

- Normalized wind area (An)
- Roof zone (1, 2, or 3)
- Panel tilt angle

🗺 Roof Zones for Solar Panels

Solar panel location on the roof determines which zone applies. Panels near edges and corners experience higher wind pressures than those in the interior field.

Zone 1 Interior Field

Panels located in the interior of the roof, away from edges. These experience the lowest wind pressures and have the lowest GCrn,nom values.

Zone 2 Roof Edges

Panels located near roof edges (excluding corners). Wind accelerates over edges, creating moderate wind pressures higher than Zone 1.

Zone 3 Roof Corners

Panels located at roof corners experience the highest wind pressures due to wind vortex formation. Highest GCrn,nom values apply.

⚠ Zone Boundaries per Figure 29.4-7

Zone boundaries are defined based on building height (h) and minimum building dimension. The edge zone width is typically calculated as 0.1 × min(building length, building width), but not less than 0.4h. Consult ASCE 7 Figure 29.4-7 for exact zone boundary definitions.

📐 Panel Tilt Angle Categories

The tilt angle (ω) of solar panels affects the applicable GCrn,nom values. ASCE 7 provides coefficients for different tilt angle ranges:

Tilt Angle Range Typical Application Wind Effect
0° - 5° Flush-mounted panels on flat roofs Minimal uplift, acts similar to roof surface
5° - 15° Low-tilt arrays, ballasted systems Moderate uplift forces begin
15° - 35° Typical tilted arrays for optimal solar gain Significant uplift and sliding forces
> 35° Steep-angle installations High uplift, may need special analysis

The tilt angle is calculated as: ω = arctan[(h2 - h1) / Lp], where h2 is the high edge height, h1 is the low edge height, and Lp is the panel chord length.

📈 Normalized Wind Area

The normalized wind area (An) is used to determine GCrn,nom from Figure 29.4-7:

An = (1000 / [max(Lb, 15)]2) × A
A = effective wind area of panel (Lp × Wp) in ft2
Lb = characteristic length = min(0.4 × √(h × WL), h, Ws)
h = mean roof height
WL = building width perpendicular to wind
Ws = building width parallel to wind

🏭 Exposed Panel Criteria

A panel is considered "exposed" (requiring γE = 1.5 for edge panels) when:

  1. d1 > 0.5 × h (setback from roof edge exceeds half the building height)

AND either:

ⓘ 24-Inch Height Threshold

Per ASCE 7-16 and 7-22, rooftop solar panel systems mounted 24 inches or less above a low-slope roof surface do not require live load modeling as a separate structure. This simplifies analysis for typical flush-mount installations.

🌏 ASCE 7-22: New Ground-Mount Provisions (Section 29.4.5)

ASCE 7-22 introduced Section 29.4.5 specifically for fixed-tilt ground-mounted solar arrays. This section did not exist in ASCE 7-16, which only addressed rooftop installations.

Key Features of Section 29.4.5

✔ Ground-Mount vs. Rooftop

Ground-mounted systems typically experience different wind flow patterns than rooftop installations because they're not influenced by building aerodynamics. Section 29.4.5 accounts for these differences with specific force coefficients.

🔄 ASCE 7-16 vs. ASCE 7-22 Comparison

Feature ASCE 7-16 ASCE 7-22
Rooftop Solar (29.4.3, 29.4.4) ✔ Included ✔ Included (refined)
Ground-Mount Solar (29.4.5) ✘ Not included ✔ NEW section
Directionality Factor (Kd) Applied separately Incorporated into calculations
Roof Zone Definitions Standard zones Simplified zone designations
Structural Load Path General requirements Panels cannot be load path unless tested
Tornado Loads (Chapter 32) ✘ Not included ✔ NEW (Risk Cat III/IV)

⚠ ASCE 7-22 Load Path Requirement

ASCE 7-22 specifies that "solar panels shall not be considered as part of the load path that resists the interconnection force unless panels have been evaluated or tested." This is an important change affecting structural design of PV mounting systems.

📝 Example Calculation

The following example demonstrates a solar panel wind load calculation for a rooftop installation:

Given Parameters:

Step-by-Step Calculation:

  1. Calculate velocity pressure (qh): qh = 32.28 psf (from ASCE 7 velocity pressure tables)
  2. Determine γp: No parapet, so γp = 0.9
  3. Calculate γc: Lp = 65"/12 = 5.42 ft
    γc = max(0.6 + 0.06 × 5.42, 0.8) = max(0.925, 0.8) = 0.925
  4. Determine γE: Assume interior panel (not at array edge), γE = 1.0
  5. Calculate normalized wind area and find GCrn,nom:
    An = 78.24 ft² → GCrn,nom = 1.607 (from Figure 29.4-7 for Zone 3, 15-35° tilt)
  6. Calculate GCrn:
    GCrn = 0.9 × 0.925 × 1.0 × 1.607 = 1.338
  7. Calculate design wind pressure:
    p = 32.28 × 1.338 = 43.2 psf

ⓘ Interpretation

The design wind pressure of 43.2 psf applies to both uplift and downward loading. The mounting system and attachments must be designed to resist these forces with appropriate safety factors per the applicable building code.

🛠 Design Considerations

Ballasted vs. Attached Systems

Rooftop solar systems are typically either ballasted (held in place by weight) or mechanically attached to the roof structure:

System Type Advantages Considerations
Ballasted No roof penetrations, easier installation Heavy weight on roof, limited to low-slope roofs, specific seismic requirements
Attached Lower weight, suitable for all roof slopes Roof penetrations required, waterproofing concerns

ⓘ Ballasted System Requirements

Per ASCE 7, ballasted systems must meet seven specific conditions for seismic compliance. The ballast weight must be sufficient to resist both uplift and sliding forces from wind loads.

Special Considerations for High-Wind Regions

Calculate Your Solar Panel Wind Loads

Use our professional wind load calculator to determine design pressures for your solar installation per ASCE 7-16 or ASCE 7-22.

Get Solar Panel Calculator

🔗 Resources and References

ⓘ Professional Engineering Note

Solar panel wind load calculations should be performed or reviewed by a licensed Professional Engineer (PE). Local jurisdictions may require stamped calculations for building permit approval. Always verify requirements with your local building department.