Home Rule State Solar Belt State Eastern Plains Tornado Risk

Colorado Wind Load Requirements

Complete guide to Colorado wind load requirements including jurisdiction-specific code adoption, ASCE 7-16/7-22 standards, the critical Ke elevation factor, Denver's 2024 IBC transition, and regional wind considerations.

Get Colorado Wind Load Calculator

No Mandatory Wind Load Permit Required

Colorado is one of 40 states where building departments do NOT require wind load calculations by law to obtain a building permit. However, you may still need wind load calculations for insurance requirements, manufacturer warranties, liability protection, or engineering best practices.

View all 40 states without mandatory wind load permits →

Colorado Code Adoption - Home Rule State

Colorado is a home rule state, meaning building codes are adopted at the local jurisdiction level rather than statewide. Each city, county, and municipality determines which edition of the International Building Code (IBC) and associated standards to adopt.

Important: Always Verify Local Requirements

Because Colorado lacks statewide code adoption, you must verify the adopted code edition with the local building department before beginning any project. Code editions can vary significantly between neighboring jurisdictions.

Key Jurisdiction Code Adoption

Aurora

Current Code: 2021 IBC

Wind Standard: ASCE 7-16

Updated: April 2023

ASCE 7-16

Denver

Current Code: 2021 IBC

Transitioning to: 2024 IBC / ASCE 7-22

Effective: December 31, 2025

ASCE 7-16 ASCE 7-22 Dec 2025

Colorado Springs

Current Code: 2021 IBC

Wind Standard: ASCE 7-16

Status: Verify locally

ASCE 7-16

Boulder

Current Code: 2021 IBC

Wind Standard: ASCE 7-16

Status: Verify locally

ASCE 7-16

Aurora Engineering Design Criteria

The City of Aurora provides specific engineering design criteria that apply to wind load calculations:

Parameter Value
Ground Snow Load (Pg) 40 psf
Basic Wind Speed (Risk Cat II) 105-110 mph
Basic Wind Speed (Risk Cat III) 110-115 mph
Basic Wind Speed (Risk Cat IV) 120-125 mph
Default Exposure Category B
Weathering Severe
Minimum Frost Depth 36 inches
Winter Design Temperature 1°F
Ice Barrier Underlayment Required
Mean Annual Temperature 50°F

Ground Elevation Factor (Ke) - Critical for Colorado

Why Ke Matters in Colorado

ASCE 7-16 introduced the Ground Elevation Factor (Ke) which adjusts velocity pressure for reduced air density at higher elevations. This is critical for Colorado projects where elevations range from 3,500 ft to over 14,000 ft.

At higher elevations, air density is lower, which reduces the force that wind exerts on structures. The Ke factor accounts for this physics-based reduction in wind pressure.

Elevation Ke Factor Pressure Reduction
Sea Level 1.00 0%
3,000 ft 0.94 6%
5,280 ft (Denver) 0.88 12%
6,000 ft 0.86 14%
8,000 ft 0.82 18%
10,000 ft 0.78 22%

ASCE 7-16 Velocity Pressure Formula

qz = 0.00256 × Kz × Kzt × Kd × Ke × V²
qz = Velocity pressure at height z (psf)
Kz = Velocity pressure exposure coefficient
Kzt = Topographic factor (typically 1.0)
Kd = Wind directionality factor (0.85 for most buildings)
Ke = Ground elevation factor (critical for Colorado!)
V = Basic wind speed (mph)

Denver Example (5,280 ft)

At Denver's "Mile High" elevation, Ke = 0.88 approximately. This results in a ~12% reduction in design wind pressures compared to an identical building at sea level. This can significantly impact product selection and structural design.

Denver's Transition to ASCE 7-22

The City and County of Denver is adopting the 2025 Denver Building Code based on the 2024 International Building Code series, which references ASCE 7-22 for wind loads.

Key Dates

July - December 2025: 6-month transition period

December 31, 2025: Full adoption effective date

2024 IBC Code Package

  • 2024 International Building Code (IBC)
  • 2024 International Energy Conservation Code (IECC)
  • 2024 International Fuel Gas Code (IFGC)
  • 2024 International Mechanical Code (IMC)
  • 2024 International Plumbing Code (IPC)
  • 2024 International Existing Building Code (IEBC)
  • 2024 International Residential Code (IRC)
  • 2024 International Fire Code (IFC)

Key Changes: ASCE 7-16 vs ASCE 7-22

Feature ASCE 7-16 ASCE 7-22
Wind Directionality (Kd) In qz equation Moved to pressure equations
Tornado Loads Commentary only New Chapter 32 (required)
C&C Roof Zones Multiple zones Reduced to 3 zones
Minimum EWA Various 10 sq ft minimum
Simplified Methods (Part 2) Available Removed
Elevated Buildings Not addressed New Section 27.3.1.1
Ground-Mounted Solar Limited guidance New Section 29.4.5

For most Colorado projects, ASCE 7-22 generally produces same or slightly lower pressures than ASCE 7-16. However, tornado loads in Chapter 32 may apply to eastern Colorado for Risk Category III and IV structures.

Windows, Doors & Fenestration Requirements

Per IBC Chapter 16, buildings, structures, and parts thereof shall be designed to withstand minimum wind loads. Wind loads on fenestration (windows, doors, skylights) shall be determined in accordance with ASCE 7 Chapters 26-30.

Design Pressure (DP) Ratings

Design Pressure (DP) equals the maximum wind pressure a window or door can resist:

DP Rating Positive Pressure Negative Pressure
DP 15 +15 psf -15 psf
DP 25 +25 psf -25 psf
DP 35 +35 psf -35 psf
DP 50 +50 psf -50 psf
DP 65 +65 psf -65 psf

Selection Rule

The product DP rating must exceed the calculated Component & Cladding (C&C) pressure for that location. Zone 5 corners require higher ratings than Zone 4 field areas.

Impact Resistance - NOT Required in Colorado

Colorado is NOT within a wind-borne debris region

Wind-borne debris regions are defined as areas within 1 mile of coastal mean high water line where V ≥ 130 mph, areas where V ≥ 140 mph, and Hawaii.

Since Colorado is an inland state without hurricane exposure, impact-resistant glazing and hurricane shutters are NOT required by code. Standard wind load design provisions apply.

Deflection Limits for Fenestration

When framing members support glass:

Span Length Maximum Deflection
Up to 13'-6" L/175
Over 13'-6" L/240 + 1/4"

Applied at 0.6 times the C&C wind loads

Roofing Requirements & Standards

IBC Chapter 15 provides minimum requirements for the design and construction of roof assemblies and rooftop structures. The following ICC/IBC references apply to Colorado projects based on locally adopted code editions.

IBC 2024 Chapter 15 - Section 1504 Performance Requirements

Section 1504.1 General:

"Roof decks and roof coverings shall be designed for wind loads in accordance with Chapter 16 and Sections 1504.2, 1504.3, and 1504.4."

Section 1504.3 Wind Resistance of Non-ballasted Roofs:

Roof coverings mechanically attached or adhered to the roof deck shall be designed to resist the design wind load pressures for components and cladding per Section 1609.5.2.

Asphalt Shingles (IBC Section 1504.2)

Wind Speed Required Classification Test Standard
≤ 110 mph Class D ASTM D7158
> 110 mph to ≤ 120 mph Class G or H ASTM D7158
> 120 mph Class H ASTM D7158

Standard calculations assume Exposure B or C, height ≤ 60 ft. Additional calculations required for other conditions.

Clay and Concrete Tile (IBC Section 1504.3)

  • Wind loads per IBC Section 1609.6
  • Testing per SBCCI SSTD 11 or ASTM C1568 (overturning resistance)
  • Wind tunnel testing per ASTM C1569 for tiles not meeting Chapter 16 limitations

Slate Shingles (IBC Section 1504.4.4) NEW in IBC 2024

  • Testing per ASTM D3161 (Fan-Induced Method)
  • Classification per IBC Table 1504.2

Metal Edge Systems

  • Design per IBC Chapter 16
  • Testing per ANSI/SPRI ES-1 (Methods RE-1, RE-2, RE-3)

UL 580 - Roof Uplift Resistance Standard

UL 580 (Standard for Tests for Uplift Resistance of Roof Assemblies) classifies roof assemblies by uplift resistance:

UL 580 Class Uplift Pressure Rating
Class 15 15 psf
Class 30 30 psf
Class 60 60 psf
Class 90 90 psf
Class 120 120 psf

UL 580 Test Procedure

  • Specimen Size: 10 ft × 10 ft (100 sq ft) test specimen
  • Loading: Static and dynamic (cyclic) pressure loading
  • Criteria: Assembly must maintain attachment integrity without excessive deflection

Tornado Load Provisions (ASCE 7-22 Chapter 32)

Eastern Colorado Tornado Considerations

Chapter 32 of ASCE 7-22 introduces tornado load requirements:

  • Design required where tornado speed (VT) > 60 mph
  • Applies to Risk Category III and IV structures
  • Primarily affects areas east of the Rocky Mountains
  • Higher uplift classifications may be needed in tornado-prone regions

For Colorado: Most of Colorado west of the mountains is outside the primary tornado corridor, but eastern Colorado (plains region) may require tornado load consideration for certain building types.

Roofing Reference Standards Summary

Standard Description Application
ASTM D7158 Wind Resistance of Asphalt Shingles Shingle classification (D, G, H)
ASTM D3161 Wind-Resistance of Steep Slope Roofing (Fan-Induced) Slate shingles
ASTM C1568 Concrete/Clay Roof Tile Wind Resistance Tile overturning resistance
ASTM C1569 Concrete/Clay Tile Wind Tunnel Testing Non-standard tile configurations
SBCCI SSTD 11 Wind Resistance of Concrete/Clay Tile Alternative to ASTM C1568
ANSI/SPRI ES-1 Wind Design Standard for Edge Systems Metal edge, fascia, coping
UL 580 Tests for Uplift Resistance of Roof Assemblies Complete roof assembly classification

Colorado Exposure Categories

Category Description Typical Colorado Application
Exposure B Urban/suburban, wooded areas Default for most Front Range cities
Exposure C Open terrain, grasslands Eastern plains, mountain valleys
Exposure D Flat, unobstructed coastal areas Not applicable in Colorado

High Wind Areas in Colorado

Certain Colorado locations experience elevated wind speeds:

  • Mountain passes and ridges - can experience extreme wind events
  • Foothill transitions (Boulder, Golden) - Chinook/downslope winds
  • Eastern plains - tornado potential and open exposure

Always Verify Site-Specific Wind Speeds

Use ASCE 7 wind speed maps or the ASCE 7 Hazard Tool to determine accurate wind speeds for your specific project location.

Colorado Solar PV Wind Load Requirements

Colorado is a leading state for solar energy with over 300 days of sunshine annually. The state's high elevation and abundant sunlight make it an ideal location for both residential and utility-scale solar installations. Understanding wind load requirements is critical for proper solar panel design and installation.

Why Solar Wind Loads Matter in Colorado

  • Elevation Benefit: The Ke factor reduces wind pressures by up to 22% at 10,000 ft elevation
  • Mountain Winds: Chinook and downslope winds can produce localized high-wind events
  • Utility-Scale Projects: Large solar farms on the Eastern Plains require careful exposure analysis
  • ASCE 7-22: New Section 29.4.5 provides guidance for ground-mounted fixed-tilt systems

ASCE 7 Solar Panel Provisions

Section Application Description
29.4.3 Low-Slope Roofs (≤ 7°) Rooftop solar on flat or nearly flat roofs
29.4.4 Parallel to Roof Surface Flush-mounted panels on any roof slope
29.4.5 Ground-Mounted (ASCE 7-22) Fixed-tilt ground-mount systems
Chapter 27 Ground-Mounted (≤ 45°) Treated as open building with monoslope roof

Solar Wind Pressure Formula

ASCE 7 Solar Panel Wind Pressure

p = qh × GCp × γE × γA
p = Design wind pressure on solar panels (psf)
qh = Velocity pressure at mean roof height (includes Ke for Colorado!)
GCp = External pressure coefficient
γE = Edge factor (accounts for panel position)
γA = Array edge factor

Colorado Elevation Advantage for Solar

Colorado's high elevation provides a unique advantage for solar installations. The Ke ground elevation factor reduces velocity pressure, which directly reduces design wind loads on solar panels:

  • Denver (5,280 ft): ~12% reduction in wind pressure vs. sea level
  • Leadville (10,150 ft): ~22% reduction in wind pressure vs. sea level

This can result in lower design pressure requirements and potentially more economical mounting systems.

Learn more about Solar Belt wind load requirements →

Need Colorado Wind Load Calculations?

Our professional ASCE 7 wind load calculators account for Colorado's unique elevation factors, exposure categories, and jurisdiction-specific requirements.

Get Wind Load Calculator